20K-160kVA PF=1.0/3:3/Online High Frequency Modular UPS, Dual-mains Input

Delivery term:The date of payment from buyers deliver within days
  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers deliver within days

  • seat:

    Beijing

  • Validity to:

    Long-term effective

  • Last update:

    2017-08-09 19:36

  • Browse the number:

    197

Send an inquiries
+
American Wise Power Technologies, Inc
Contactaixin:

Contactaixin:

eastsolar(Ms.)  

telephone:

Area:

Beijing

Address:

1418 Lexington Street, Tustin, California, United States

Website:

http://eastsolar.anjujc.com/

+
Model Number: MOD 20K~80K/100K~160KVA (3:3) Brand Name: AWP Key Specifications/Special Features: Modular 20 series UPS is redundant, scalable, 3-phase UPS power protection system with on-line double-conversion and full DSP control technology and highly enhanced output power factor to 1.0, hot-swappable and flexible power module configuration makes capacity scalable from 20/20kW up to 160/160kW and system capacity can be expanded to 320/320kW by advanced N + X wireless parallel and redundancy technology, all internal modules (monitoring module, power module and charging module) are modularly designed and hot-swappable, assuring system compactness, reliability and easy maintenance, modular 20 series UPS was specifically designed to ensure maximum protection of mission critical data center or critical applications loadsHighlights:Hot-swappable modularityEasy expandability and scalabilityHigh power densityHigh output power factor (PF1.0)
  • Integrated power distribution
  • Dual-mains input
  • Small footprint
  • Model MOD 80 MOD 160
    Capacity 20-80kVA
    20-80KW
    20-160kVA
    20-160kW
    Numbers of parallel module 1-4 1-8
    Numbers of redundancy module 0-3 0-7
    Rated capacity of each power module 20kVA/20kW
    Input:
    Rated voltage 380/400/415V AC
    Voltage range 204-242 V AC (load ≤ 50%)
    242-277V AC (50% < load ≤ 70%)
    277-520V AC (70% < load ≤ 100%)
    Rated frequency 50/60Hz (auto-sense)
    Frequency range 40-70Hz
    Power factor ≥ 0.99
    Bypass voltage range ≤ 3%
    Delayed start of rectifier rated output voltage: - 40%- + 20% (settable via LCD)
    Output
    Voltage 380/400/415V AC
    Voltage regulation ± 1%
    Frequency battery mode: 50/60Hz ± 0.1%
    mains mode: synchronized with utility
    frequency conversion mode: 50Hz input and 60Hz output or 60Hz input and 50Hz output
    Waveform sinusoidal
    Power factor 0.9
    Crest factor 3:1
    Total harmonic distortion (THDV) ≤ 2% (linear load)
    ≤ 5% (non-linear load)
    Transfer time AC mode to battery mode: 0 minute
    inverter mode to bypass mode: 0 minute
    inverter mode to eco-friendly mode: 5-10 minutes
    Inverter overload capability 105%: longtime running
    105-110%: transfer to bypass in 1H
    110-125%: transfer to bypass in 10 minutes
    125-150%: transfer to bypass in 1 minute
    150-200%: transfer to bypass in 200 minutes
    > 200%: transfer to bypass in 100 ms
    Slight adjustment of inverter output voltage ± 5V
    Batteries
    DC voltage ± 240V DC (± 192 / ± 204 / ± 216 / ± 228V DC selectable)
    Inbuilt battery of standard model 12V/9Ah x 40 for each module
    Charging current 1-30/60 A (settable via LCD)
    System
    Efficiency ≥94%
    Display panel 5.7 inches LCD touchscreen
    Protections short-circuit, overload, over-temperature, overvoltage, under voltage, IGBT pulse -by pulsecurrent limiting, early warning of battery low voltage and battery overcharge protections
    Alarm battery mode, low battery, fans fault
    EMI EN62040-2
    EMS IEC61000-4-2 (ESD)
    IEC61000-4-3 (RS)
    IEC61000-4-4 (EFT)
    IEC61000-4-5 (Surge)
    Communications
    RS232/RS485/USB/dry contacts (standard) supports Windows 98/2000/2003/XP/Vista/2008/7/8/10
    SNMP (option) power management from SNMP manager and web browser
    Others
    Humidity 0-95% RH at 0-40℃ (non-condensing)
    Noise level ≤ 60dB
    Module dimensions (W) 482 x (D) 590 x (H) 590mm
    Module weight 28kg/power module, 27 kg / charger module, 7kg /monitoring module
    UPS dimensions (W) 600 x (D) 1000 x (H) 1600mm (W) 600 x (D) 1000 x (H) 2000mm
    UPS packing (W) 700 x (D) 1070 x (H) 1070mm (W) 700 x (D) 1070 x (H) 2060mm
    UPS weight
    Without inbuilt battery and power module
    Net weight: 225kg
    Gross weight: 245kg
    Net weight: 290kg
    Gross weight: 310kg
    Input /output/bypass breaker Yes Yes
    Shipping Information:
    • FOB Port: Shenzhen
    • Lead Time: 15 - 30 days
    Main Export Markets:
    • Asia
    • Australasia
    • Central/South America
    • Eastern Europe
    • Mid East/Africa
    • North America
    • Western Europe